A power plant turns heat into work; a refrigerator uses work to take heat out of a cold space. Both are cycles: the fluid goes through several devices and returns to its initial state. Here each device is analyzed as a control volume, we see why no real cycle reaches the Carnot cycle, and the three cycles of the simulator —Rankine, Brayton and vapor-compression refrigeration— are solved with real properties.

What a cycle is and why a cold reservoir is needed

In a cycle the fluid returns to its starting state: over one turn its energy does not change and the net heat received equals the net work delivered. The thermal efficiency is the fraction of the heat received that becomes work:

Why can not be zero? The heat entering at brings at least of entropy and work carries none. For the fluid to return to its state that entropy has to leave with another heat, rejected at a lower temperature . Hence the limit of every heat engine (Kelvin–Planck):

Hot reservoir THCold reservoir TLEngineQH QL WHeat engineW = QH − QL Warm surroundings THCold space TLR / HPQH QL WRefrigerator or heat pumpW = QH − QL
A heat engine takes , delivers and rejects ; a refrigerator or heat pump receives to carry from the cold space to the surroundings.

The refrigerator and the heat pump are the same cycle run backwards. They are measured by the coefficient of performance (COP), which can exceed 1 because it is not an efficiency; the same entropy argument gives its limit:

Devices as control volumes

Each device is analyzed as a steady-flow control volume: one inlet, one outlet, the same flow and nothing changes with time. The first law per kilogram uses the enthalpy , not : the term is the work of pushing the fluid in and out.

Pumps, turbines and compressors are insulated and fast: they are taken as adiabatic (). Heat exchangers have no shafts: . Each device reduces to a difference of enthalpies:

BoilerCondenserTurbinePumpqin qout wt wp 1234
Steam power plant (Rankine cycle): pump 1→2, boiler 2→3, turbine 3→4 and condenser 4→1.
DeviceAssumptionEquation (per kg)Cycle
Pumpadiabatic, liquidRankine
Boiler, combustor, constant Rankine, Brayton
TurbineadiabaticRankine, Brayton
Compressoradiabatic, gas or vaporBrayton, refrigeration
Condenser, constant Rankine, refrigeration
Evaporator, constant refrigeration
Expansion valve, refrigeration
Regeneratoradiabatic to the outsidewhat one stream gives the other receivesBrayton
Cycles use positive magnitudes (, , , ) and the name gives the direction, as in the simulator. Check of any solution: .

Isentropic processes and isentropic efficiencies

An adiabatic and reversible process is isentropic (): the ideal reference for turbines, compressors and pumps. Friction and turbulence generate entropy, so the actual turbine gives less work and the compressor needs more. The isentropic efficiency compares them between the same pressures, so that it is always below 1:

shhigh Plow PTurbine34s4Δhsactual Δhηt = Δhreal / Δhsshhigh Plow PCompressor or pump12s2Δhsactual Δhηc = Δhs / Δhreal
On the h–s diagram the isentropic process is a vertical line (dashed); the actual one ends at the same pressure but to the right, with more entropy.

For the pump, with gives , and a liquid hardly changes its volume:

With a gas that integral is huge ( about a thousand times that of a liquid): compressing vapor or air costs a lot and pumping water almost nothing. It is the essential difference between the Rankine and the Brayton cycles.

Exam tip: in the turbine the actual work is times the isentropic one; in the compressor and the pump, the isentropic one divided by . The actual exit state is found with and , never with .

The Carnot cycle: the limit

The Carnot cycle (two isotherms and two isentropic processes) is a rectangle on the T-s diagram. Since , the enclosed area is the net work and the efficiency is , the highest between those temperatures. Any other cycle receives part of its heat below ; with the mean temperatures at which heat enters and leaves it becomes a Carnot cycle between them:

Why is it not built? With steam, heat can be received and rejected at constant temperature inside the dome, but a mixture of liquid and vapor would have to be compressed (neither a pump nor a compressor does it well) and the top temperature could not exceed the critical one (374 °C). With a gas, receiving heat at constant temperature requires extremely slow processes. Real cycles replace the isotherms by constant-pressure processes, and every improvement (superheating, raising the boiler pressure, lowering the condenser pressure, reheating, regenerating) raises or lowers .

The ideal Rankine cycle

1→2 isentropic compression of the liquid in the pump; 2→3 boiler at constant pressure (the liquid warms up, boils and is superheated); 3→4 isentropic expansion in the turbine; 4→1 condensation to saturated liquid:

0123456789050100150200250300350400s (kJ/kg·K)T (°C)T̄H = 220.1 °C1, 234Carnot between 91.8 °C and 350 °C: η = 41.4 %Rankine: η = 26.0 %domeTL = 91.8 °C
Cycle of example 1 (3 MPa, 350 °C, 75 kPa) on the real water dome, computed with the properties of the simulator; the shaded area is . The dashed rectangle is the Carnot cycle between the same extreme temperatures: the Rankine cycle receives heat on average at only 220.1 °C (), which is why it gives 26.0 % and not 41.4 %.

Pump work versus turbine work

The back work ratio is the part of the turbine work spent on the pump or compressor: 0.43 % in example 1, 40.2 % in the ideal gas turbine of example 3 and 59.2 % if its compressor is 80 % and its turbine 85 % (the efficiency then falls from 42.6 % to 26.6 %). In the Rankine cycle the pump efficiency hardly matters; in the Brayton cycle that of the compressor is decisive.

How to raise the efficiency

Change to example 1 (in the simulator)ηTurbine exitWhy
Base: 3 MPa, 350 °C, 75 kPa26.0 %—
Condenser at 10 kPa33.4 %lowers : it condenses at 45.8 °C, not 91.8 °C
Steam at 600 °C30.3 %vapor at 101.7 °Craises ; the expansion ends outside the dome
Boiler at 10 MPa31.7 %raises (it boils at 311.0 °C), but the exit is wetter
All three: 10 MPa, 600 °C, 10 kPa41.7 %the effects add up
With more than 10–12 % droplets at the exit, the turbine blades erode (the simulator warns below ). Raising the boiler pressure improves η but lowers : power plants solve it with reheat.

Reheat

The steam expands in a high-pressure turbine to an intermediate pressure, returns to the boiler, is reheated (almost always to the inlet temperature) and expands in a low-pressure turbine to the condenser. Both heats and both works must be added:

01234567890100200300400500600s (kJ/kg·K)T (°C)1, 234564′no reheat: η = 43.0 %, x₄′ = 0.804reheated at 4 MPa: η = 45.0 %, x₆ = 0.896
15 MPa, 600 °C and 10 kPa, ideal, with real properties. Without reheat (red) the expansion 3→4′ ends with 19.6 % liquid; reheating at 4 MPa to 600 °C the exit 6 has . The main effect is drying the steam: the efficiency rises only a little, from 43.0 % to 45.0 %.

How to read each state

Each state is fixed by two independent properties. Solving a cycle by hand is knowing which ones are known at each point, which region it is in and which table to use:

StateKnownRegion and tableHow it is obtained
Rankine 1condenser , saturation by pressure, ,
Rankine 2boiler , compressed liquid; actual:
Rankine 3 and 5, : superheatedsteam table, interpolating between rows or blocks
Rankine 4s, compare with and mixture: , ; if , interpolate in
Rankine 4 actual and (from the efficiency)compare with and
Refrigeration 1 and , or saturation or superheated, , or the superheated table
Refrigeration 3 and , or saturation or compressed liquid, or if subcooled
Refrigeration 4, mixture
Brayton (air) (and )ideal gasair table: , ; isentropic:
The values of and depend on the reference state of each table (where the zero is placed), but their differences do not. For water the simulator uses and for saturated liquid at the triple point, and for R-134a the ASHRAE reference ( and for saturated liquid at −40 °C). Another table gives other numbers at each state, but the same , , η and COP: do not mix tables in one problem. To see it, in «Thermodynamic tables» change the «Reference state of h and s» of a refrigerant (ASHRAE, IIR or NBP).

The dome, the quality, the region of a state and interpolation are explained in the properties topic:

The Brayton cycle

It is the cycle of gas turbines: a compressor takes in air, fuel is burned in the combustor at nearly constant pressure and the gases expand in a turbine that drives the compressor and delivers the rest. It is studied with the air-standard model: air as an ideal gas throughout, combustion as a heat at constant pressure and the exhaust as a heat rejected that returns the air to state 1.

wnet RegeneratorCombustorqin exhaust125346CompressorTurbine
Gas turbine with a regenerator: the exhaust (4) preheats the compressed air (2→5) before combustion. Without a regenerator, 2 goes straight to the combustor and 4 to the exhaust.

Cold-air standard: where comes from

With constant and , and the heats are and . Between the same pressures , so and the brackets cancel:

The ideal efficiency depends only on , not on , but the net work does, and it has a maximum: with , differentiating with respect to , the optimum is , exactly when .

051015202530010203040506070pressure ratio rpη (%)0100200300400w net (kJ/kg)η = 44.8 %340.6max 352.8 at rₚ = 13.0η = 1 − rₚ−(k−1)/kwnet
Cold-air standard with K, K and (curves from the formulas above). The efficiency keeps rising with , but the work per kilogram is largest at .

Variable specific heats: the air table and

The of air grows with temperature. Ideal-gas tables give and ; in an isentropic process the entropy does not change, and with the relative pressure the condition becomes a ratio read from the table:

With read and ; gives, by interpolation, and ; likewise in the turbine with . The efficiencies are then applied to the enthalpies. In example 3 the cold model gives 44.8 % and the table 42.6 %: at high temperature the of air is below 1.4.

The regenerator

If the gases leave the turbine hotter than the compressor air (), a counterflow heat exchanger uses them to preheat that air: the combustor adds less heat for the same net work. The effectiveness is the fraction achieved of the largest heating (up to ); with equal flows, what one side gains the other loses:

The last one is the cold-air standard with an ideal regenerator (, ): with and . Unlike without a regenerator, it falls as rises. When it does not work: if the air already leaves the compressor hotter than the exhaust and the heat exchanger would cool it; this happens with high pressure ratios (in the ideal cold model, from the of maximum work on). The simulator checks it and, if so, warns and does not use it.

05101520253001020304050607080pressure ratio rpη (%)rₚ = 13.0: T₄ = T₂, η = 52.0 %rₚ → 1: Carnot 76.9 %no regeneratorideal regenerator (ε = 1)here T₄ < T₂: the regeneratorwould cool the air: not used
Ideal Brayton (cold-air standard, ) without a regenerator and with an ideal one. The curves cross where ; at low the ideal regenerator approaches Carnot, but with very little work per kilogram.
00.20.40.60.811.2200400600800100012001400s (kJ/kg·K)T (K)12s2534s46P2 = 1000 kPaP1 = 100 kPagreen: the regenerator; 4→6 gives what 2→5 receives
Actual Brayton cycle with a regenerator of example 4 (air table, 85 % compressor, 88 % turbine, ε = 75 %). Thick dashed: the actual compression and expansion; thin dashed: the isentropic ones.

Vapor-compression refrigeration

The refrigerant boils in the evaporator at low pressure taking from the cold space; the compressor raises its pressure and temperature; in the condenser it rejects to the surroundings and condenses; the expansion valve lowers the pressure and returns it cold to the evaporator. Ideal cycle: 1 saturated vapor, 1→2 isentropic compression, 2→3 down to saturated liquid, 3→4 throttling.

CondenserEvaporatorCompressorValveqH qL w1234
Refrigerator or heat pump: the refrigerator uses ; the heat pump, .

The valve is isenthalpic: it has no shafts (), the fluid crosses it very fast () and the velocity hardly changes, so the first law gives . It is highly irreversible (the entropy rises), and the work a turbine could give in its place is small and does not pay for the machine.

A ton of refrigeration is 211 kJ/min = 12,000 Btu/h, the heat to freeze one short ton of water in 24 h. The refrigerant flow follows from the capacity: .

Superheat and subcooling

In real machines the vapor leaves the evaporator a few degrees superheated, so that no liquid reaches the compressor, and the liquid leaves the condenser a few degrees subcooled, so that only liquid reaches the valve. Subcooling lowers and increases without changing the work; superheat increases and also somewhat the work and the discharge temperature. The Carnot limit is then taken between (the warmest the refrigerant gets in the evaporator) and (the coldest in the condenser).

The P-h diagram

Refrigeration uses the pressure–enthalpy diagram, with pressure on a logarithmic scale: evaporator and condenser are horizontal, the valve is vertical, and the heats and the work are read as horizontal lengths. Inside the dome the pressure fixes the temperature; to the right is the superheated vapor, where the compression ends.

05010015020025030050100200500100020005000h (kJ/kg)P (kPa)critical point(101.1 °C)12341′2′3′4′qL = 143.7 kJ/kgw = 36.2qH = 179.9valve: h₄ = h₃red: with 10 °C of superheatand 8 °C of subcooling
Ideal R-134a cycle of example 5 (0.14 and 0.8 MPa) on the real dome. In red, with 10 °C of superheat and 8 °C of subcooling: goes from 143.7 to 163.3 kJ/kg, the work from 36.2 to 38.0 kJ/kg and the COP from 3.97 to 4.29.
For heat to flow, the refrigerant must be colder in the evaporator than the space being cooled and warmer in the condenser than the surroundings. On a hot day the condenser pressure rises, the work grows and the COP falls.

Using the simulator

It is in Engineering → Thermodynamic cycles; the results are recomputed as you type. Everything is SI: absolute pressures in kPa, temperatures in °C for Rankine and refrigeration and in kelvin for Brayton, efficiencies in % (100 % = ideal).

  • Cycle: first the family (Steam power, Gas turbines and propulsion, Refrigeration and heat pumps…) and below it the cycle: Rankine, Brayton or Refrigerator for this topic; each keeps its data. In Examples, «Load an example».
  • Rankine: «Boiler pressure» and «Turbine inlet temperature» (or the box «Saturated vapor to the turbine (no superheat)»), «Condenser pressure» (saturated liquid leaves it), «Turbine (isentropic)», «Pump (isentropic)», «Net power (optional)» in MW and the box «With reheat», which opens «Reheat pressure» and «Reheat temperature» (it proposes the geometric mean of the pressures). The turbine efficiency applies to both turbines.
  • Brayton: Air model «Variable specific heats» (air table) or «Cold-air standard» (asks for k = cₚ/cᵥ and cₚ); «Compressor inlet T₁», «Pressure P₁», «Pressure ratio rₚ», «Turbine inlet T₃»; «Compressor (isentropic)», «Turbine (isentropic)», «Regenerator (effectiveness)» (0 % = none) and «Net power (optional)».
  • Refrigerator: the «Fluid» (any refrigerant of the tables); By pressures or By temperatures of saturation (switching converts the values); «Compressor (isentropic)», «Cooling capacity» in kW (empty = results per kg; tons × 3.517), «Superheat» and «Subcooling» in °C.
  • Results: cards (efficiency with Carnot, net work, heats, exit quality, «Back work ratio», flow if a power or capacity is given; in refrigeration «Refrigeration COP», «Heat-pump COP», «Refrigerating effect», «Quality after the valve» and in kW and tons); Diagrams T-s (and P-h in refrigeration) with the real dome, thick dashed for the actual process and thin for the isentropic one; Cycle states (P, T, h, s, quality or , description); Step by step; and Detailed solution (PDF), with each state read and interpolated in the table, the balances and the checks.
  • Warnings (⚠): exit quality below ~88 %, negative net work, useless regenerator (), discharge above 140 °C. An impossible value (turbine below boiling, a reheat that cools, superheat larger than the difference between condensing and evaporating, an efficiency outside 1–100 %) gives a message that names the field and explains why.

Common mistakes

  • Applying the efficiency the wrong way: turbine ; compressor and pump .
  • Finding the actual turbine exit with (that is the isentropic one) instead of with and .
  • Forgetting in the reheat , or the work of the high-pressure turbine.
  • Using °C in , in or in the Carnot COP.
  • With variable specific heats, using instead of .
  • Using a regenerator with , or computing from when there is one (it is from ).
  • Taking after the valve: it is a mixture with .
  • Confusing tons of refrigeration with kW, or mixing refrigerant tables with different references.

Worked examples

Example 1Ideal Rankine cycle

An ideal Rankine cycle receives steam at 3 MPa and 350 °C in the turbine and condenses at 75 kPa. Find the works, the heat received, the efficiency, the exit quality and the back work ratio, and compare with Carnot.

Solution

  1. State 1, saturated liquid at 75 kPa: °C, kJ/kg, m³/kg, kJ/kg·K.
  2. Pump: kJ/kg and kJ/kg.
  3. State 3: at 3 MPa water boils at 233.85 °C, so at 350 °C it is superheated vapor: kJ/kg, kJ/kg·K.
  4. State 4: lies between and at 75 kPa: and kJ/kg.
  5. , , and kJ/kg .
  6. %; %; Carnot: %.
% (Carnot 41.4 %), kJ/kg, , %.

Solve it in Simuveliq

  1. Steam power → Rankine, «Load an example» → Ideal Rankine: 3 MPa, 350 °C, 75 kPa.
  2. Cards: 26.02 % (Carnot 41.44 %), 710 kJ/kg, «Exit quality» 88.61 %, back work 0.4252 %. The step by step compares = 3.032 kJ/kg with = 3.034 kJ/kg.

Example 2Plant with reheat and real turbines

A 150 MW (net) plant: steam at 15 MPa and 600 °C to the high-pressure turbine, expansion to 3 MPa, reheat to 600 °C and expansion to 10 kPa. Turbines at 88 % and pump at 90 %. Find the efficiency, the exit quality, the steam flow and the boiler heat, and compare without reheat.

Solution

  1. State 1 (10 kPa, ): kJ/kg, m³/kg. Pump: kJ/kg (the equation of state gives 15.10: the liquid is slightly compressed); kJ/kg and kJ/kg.
  2. State 3: kJ/kg, . At 3 MPa, : superheated; interpolating, kJ/kg. kJ/kg (358.8 °C).
  3. State 5 (3 MPa, 600 °C): , . At 10 kPa: , ; kJ/kg and .
  4. kJ/kg; kJ/kg; kJ/kg and %.
  5. kg/s and MW (223.2 MW to the condenser).
  6. Without reheat: (below the erosion limit), % and kg/s. Reheat dries the steam, raises η by 2.4 points and saves 19 % of the flow.
%, , kg/s, MW (no reheat: 37.8 %, ).

Solve it in Simuveliq

  1. The button opens the case; by hand: 15000 kPa, 600 °C, 10 kPa, «Turbine (isentropic)» 88, «Pump (isentropic)» 90, «Net power (optional)» 150 and «With reheat» with 3000 kPa and 600 °C.
  2. Cards: 40.2 %, «Exit quality» 98.02 %, «Steam flow» 95.18 kg/s with 373.2 and 223.2 MW; six states in the table. Untick «With reheat»: 37.78 %, 117.6 kg/s and the warning «The quality at the turbine exit is 87.8 %…».

Example 3Ideal Brayton: air table versus cold-air standard

An ideal gas turbine takes air at 100 kPa and 300 K, with and 1300 K at the turbine inlet. With the air table find , , the works, η and the back work ratio, and compare with the cold-air standard (, kJ/kg·K).

Solution

  1. At 300 K: kJ/kg, . gives K and kJ/kg.
  2. At 1300 K: kJ/kg, . gives K and kJ/kg.
  3. , , and kJ/kg: % and %.
  4. Cold air: , K, K, % and kJ/kg. It overestimates η by 2.3 points and gives an exhaust 53 K colder.
Table: K, K, kJ/kg, %, %. Cold: 543.4 K, 717.7 K, 340.6 kJ/kg, 44.8 %.

Solve it in Simuveliq

  1. Gas turbines and propulsion → Brayton, «Load an example» → Ideal Brayton: rp = 8, 300 K and 1300 K (variable specific heats): 42.55 %, «T₂ · T₄» 539.8 · 770.3 K, back work 40.24 %; the states table has the column.
  2. Press «Cold-air standard» in Air model: 44.8 %, 543.4 · 717.7 K and 340.6 kJ/kg.

Example 4Real gas turbine with a regenerator

25 MW (net) gas turbine: air at 100 kPa and 300 K, , 1400 K at the turbine, 85 % compressor, 88 % turbine and a regenerator of effectiveness 75 %. With variable specific heats find the temperatures, η with and without the regenerator and the air flow. Would the regenerator help with ?

Solution

  1. : K, kJ/kg; kJ/kg ( K).
  2. At 1400 K: kJ/kg, ; : K, ; kJ/kg ( K).
  3. , so the regenerator helps: kJ/kg ( K) and kJ/kg ( K).
  4. , , kJ/kg ( %). With the regenerator and %; without it and %.
  5. kg/s and MW (75.63 MW without the regenerator).
  6. With : K and K. The exhaust is colder than the compressed air: the regenerator cannot be used and η stays at 37.0 %.
K, K, K; % (33.1 % without the regenerator); kg/s. With it does not help ().

Solve it in Simuveliq

  1. The button opens the case: «Variable specific heats», 300 K, 100 kPa, rₚ = 10, 1400 K, «Compressor (isentropic)» 85, «Turbine (isentropic)» 88, «Regenerator (effectiveness)» 75, «Net power (optional)» 25.
  2. Cards: 42.57 %, «T₂ · T₄» 621 · 864.5 K, back work 52.91 %, «Air flow» 85.35 kg/s with 58.72 MW. Regenerator at 0: 33.06 %. With rₚ = 25 the warning «With T₄ = 716.9 K ≤ T₂ = 808.1 K the regenerator cannot heat the compressor air: it is not used» appears.

Example 5Ideal R-134a refrigerator

An R-134a refrigerator follows the ideal cycle between 0.14 and 0.8 MPa with 0.05 kg/s. Find the cooling capacity, the compressor power, the heat to the surroundings, the COP and the Carnot COP.

Solution

  1. State 1, saturated vapor at 0.14 MPa: °C, kJ/kg, kJ/kg·K.
  2. State 2: 0.8 MPa with , superheated; interpolating, kJ/kg and °C.
  3. State 3, saturated liquid at 0.8 MPa: kJ/kg ; at 0.14 MPa, .
  4. , , kJ/kg; (heat pump: 4.97).
  5. kW (2.04 tons), kW and kW.
  6. Carnot between 254.39 K and 304.48 K: ; the cycle reaches 78 % of it (losses in the valve and in the superheated vapor cooled in the condenser).
kW, kW, kW, (Carnot 5.08).

Solve it in Simuveliq

  1. Refrigeration and heat pumps → Refrigerator, «Load an example» → Ideal R-134a between 0.14 and 0.8 MPa, 0.05 kg/s: «Refrigeration COP» 3.968 (Carnot 5.079), «Heat-pump COP» 4.968, T₂ = 38.98 °C, «Quality after the valve» 0.3225 and = 7.184 kW (2.043 tons).
  2. Type «Superheat» 10 and «Subcooling» 8 to see the red cycle of the P-h figure (COP 4.295).

Example 62-ton freezer with superheat and subcooling

A 2-ton R-134a freezer evaporates at −20 °C and condenses at 35 °C; the vapor leaves the evaporator superheated by 4 °C, the liquid leaves the condenser subcooled by 5 °C and the compressor is 82 %. Find the flow, the compressor power and discharge temperature, the heat to the surroundings, the COPs and the Carnot COP.

Solution

  1. kW. Pressures: kPa and kPa.
  2. State 1: 132.7 kPa and −16 °C, superheated: kJ/kg, kJ/kg·K.
  3. Compressor: kJ/kg at 887.0 kPa with ; kJ/kg, kJ/kg and °C.
  4. State 3: 887.0 kPa and 30 °C, compressed liquid: kJ/kg (the equation of state gives 93.57) .
  5. and kJ/kg; kg/s, kW and kW.
  6. and ; Carnot between K and K: .
kg/s, kW, °C, kW, , (Carnot 5.59).

Solve it in Simuveliq

  1. The button opens the case: R-134a, By temperatures −20 and 35 °C, «Compressor (isentropic)» 82, «Superheat» 4, «Subcooling» 5 and «Cooling capacity» 7.0337 kW (2 × 3.51685).
  2. Cards: COP 3.01 (Carnot 5.59), «Heat-pump COP» 4.01, «Compressor work» 49.21 kJ/kg with T₂ = 55.65 °C and «Refrigerant flow» 0.04749 kg/s with 7.034 kW (2 tons) and 2.337 kW. The table describes state 1 as «Vapor superheated by 4 °C» and state 3 as «Liquid subcooled by 5 °C».