Thermodynamic cycles: Rankine, Brayton and refrigeration
A power plant turns heat into work; a refrigerator uses work to take heat out of a cold space. Both are cycles: the fluid goes through several devices and returns to its initial state. Here each device is analyzed as a control volume, we see why no real cycle reaches the Carnot cycle, and the three cycles of the simulator —Rankine, Brayton and vapor-compression refrigeration— are solved with real properties.
What a cycle is and why a cold reservoir is needed
In a cycle the fluid returns to its starting state: over one turn its energy does not change and the net heat received equals the net work delivered. The thermal efficiency is the fraction of the heat received that becomes work:
Why can not be zero? The heat entering at brings at least of entropy and work carries none. For the fluid to return to its state that entropy has to leave with another heat, rejected at a lower temperature . Hence the limit of every heat engine (Kelvin–Planck):
The refrigerator and the heat pump are the same cycle run backwards. They are measured by the coefficient of performance (COP), which can exceed 1 because it is not an efficiency; the same entropy argument gives its limit:
Devices as control volumes
Each device is analyzed as a steady-flow control volume: one inlet, one outlet, the same flow and nothing changes with time. The first law per kilogram uses the enthalpy , not : the term is the work of pushing the fluid in and out.
Pumps, turbines and compressors are insulated and fast: they are taken as adiabatic (). Heat exchangers have no shafts: . Each device reduces to a difference of enthalpies:
| Device | Assumption | Equation (per kg) | Cycle |
|---|---|---|---|
| Pump | adiabatic, liquid | Rankine | |
| Boiler, combustor | , constant | Rankine, Brayton | |
| Turbine | adiabatic | Rankine, Brayton | |
| Compressor | adiabatic, gas or vapor | Brayton, refrigeration | |
| Condenser | , constant | Rankine, refrigeration | |
| Evaporator | , constant | refrigeration | |
| Expansion valve | , | refrigeration | |
| Regenerator | adiabatic to the outside | what one stream gives the other receives | Brayton |
Isentropic processes and isentropic efficiencies
An adiabatic and reversible process is isentropic (): the ideal reference for turbines, compressors and pumps. Friction and turbulence generate entropy, so the actual turbine gives less work and the compressor needs more. The isentropic efficiency compares them between the same pressures, so that it is always below 1:
For the pump, with gives , and a liquid hardly changes its volume:
With a gas that integral is huge ( about a thousand times that of a liquid): compressing vapor or air costs a lot and pumping water almost nothing. It is the essential difference between the Rankine and the Brayton cycles.
The Carnot cycle: the limit
The Carnot cycle (two isotherms and two isentropic processes) is a rectangle on the T-s diagram. Since , the enclosed area is the net work and the efficiency is , the highest between those temperatures. Any other cycle receives part of its heat below ; with the mean temperatures at which heat enters and leaves it becomes a Carnot cycle between them:
Why is it not built? With steam, heat can be received and rejected at constant temperature inside the dome, but a mixture of liquid and vapor would have to be compressed (neither a pump nor a compressor does it well) and the top temperature could not exceed the critical one (374 °C). With a gas, receiving heat at constant temperature requires extremely slow processes. Real cycles replace the isotherms by constant-pressure processes, and every improvement (superheating, raising the boiler pressure, lowering the condenser pressure, reheating, regenerating) raises or lowers .
The ideal Rankine cycle
1→2 isentropic compression of the liquid in the pump; 2→3 boiler at constant pressure (the liquid warms up, boils and is superheated); 3→4 isentropic expansion in the turbine; 4→1 condensation to saturated liquid:
Pump work versus turbine work
The back work ratio is the part of the turbine work spent on the pump or compressor: 0.43 % in example 1, 40.2 % in the ideal gas turbine of example 3 and 59.2 % if its compressor is 80 % and its turbine 85 % (the efficiency then falls from 42.6 % to 26.6 %). In the Rankine cycle the pump efficiency hardly matters; in the Brayton cycle that of the compressor is decisive.
How to raise the efficiency
| Change to example 1 (in the simulator) | η | Turbine exit | Why |
|---|---|---|---|
| Base: 3 MPa, 350 °C, 75 kPa | 26.0 % | — | |
| Condenser at 10 kPa | 33.4 % | lowers : it condenses at 45.8 °C, not 91.8 °C | |
| Steam at 600 °C | 30.3 % | vapor at 101.7 °C | raises ; the expansion ends outside the dome |
| Boiler at 10 MPa | 31.7 % | raises (it boils at 311.0 °C), but the exit is wetter | |
| All three: 10 MPa, 600 °C, 10 kPa | 41.7 % | the effects add up |
Reheat
The steam expands in a high-pressure turbine to an intermediate pressure, returns to the boiler, is reheated (almost always to the inlet temperature) and expands in a low-pressure turbine to the condenser. Both heats and both works must be added:
How to read each state
Each state is fixed by two independent properties. Solving a cycle by hand is knowing which ones are known at each point, which region it is in and which table to use:
| State | Known | Region and table | How it is obtained |
|---|---|---|---|
| Rankine 1 | condenser , | saturation by pressure | , , |
| Rankine 2 | boiler , | compressed liquid | ; actual: |
| Rankine 3 and 5 | , | : superheated | steam table, interpolating between rows or blocks |
| Rankine 4s | , | compare with and | mixture: , ; if , interpolate in |
| Rankine 4 actual | and (from the efficiency) | compare with and | |
| Refrigeration 1 | and , or | saturation or superheated | , , or the superheated table |
| Refrigeration 3 | and , or | saturation or compressed liquid | , or if subcooled |
| Refrigeration 4 | , | mixture | |
| Brayton (air) | (and ) | ideal gas | air table: , ; isentropic: |
The dome, the quality, the region of a state and interpolation are explained in the properties topic:
The Brayton cycle
It is the cycle of gas turbines: a compressor takes in air, fuel is burned in the combustor at nearly constant pressure and the gases expand in a turbine that drives the compressor and delivers the rest. It is studied with the air-standard model: air as an ideal gas throughout, combustion as a heat at constant pressure and the exhaust as a heat rejected that returns the air to state 1.
Cold-air standard: where comes from
With constant and , and the heats are and . Between the same pressures , so and the brackets cancel:
The ideal efficiency depends only on , not on , but the net work does, and it has a maximum: with , differentiating with respect to , the optimum is , exactly when .
Variable specific heats: the air table and
The of air grows with temperature. Ideal-gas tables give and ; in an isentropic process the entropy does not change, and with the relative pressure the condition becomes a ratio read from the table:
With read and ; gives, by interpolation, and ; likewise in the turbine with . The efficiencies are then applied to the enthalpies. In example 3 the cold model gives 44.8 % and the table 42.6 %: at high temperature the of air is below 1.4.
The regenerator
If the gases leave the turbine hotter than the compressor air (), a counterflow heat exchanger uses them to preheat that air: the combustor adds less heat for the same net work. The effectiveness is the fraction achieved of the largest heating (up to ); with equal flows, what one side gains the other loses:
The last one is the cold-air standard with an ideal regenerator (, ): with and . Unlike without a regenerator, it falls as rises. When it does not work: if the air already leaves the compressor hotter than the exhaust and the heat exchanger would cool it; this happens with high pressure ratios (in the ideal cold model, from the of maximum work on). The simulator checks it and, if so, warns and does not use it.
Vapor-compression refrigeration
The refrigerant boils in the evaporator at low pressure taking from the cold space; the compressor raises its pressure and temperature; in the condenser it rejects to the surroundings and condenses; the expansion valve lowers the pressure and returns it cold to the evaporator. Ideal cycle: 1 saturated vapor, 1→2 isentropic compression, 2→3 down to saturated liquid, 3→4 throttling.
The valve is isenthalpic: it has no shafts (), the fluid crosses it very fast () and the velocity hardly changes, so the first law gives . It is highly irreversible (the entropy rises), and the work a turbine could give in its place is small and does not pay for the machine.
A ton of refrigeration is 211 kJ/min = 12,000 Btu/h, the heat to freeze one short ton of water in 24 h. The refrigerant flow follows from the capacity: .
Superheat and subcooling
In real machines the vapor leaves the evaporator a few degrees superheated, so that no liquid reaches the compressor, and the liquid leaves the condenser a few degrees subcooled, so that only liquid reaches the valve. Subcooling lowers and increases without changing the work; superheat increases and also somewhat the work and the discharge temperature. The Carnot limit is then taken between (the warmest the refrigerant gets in the evaporator) and (the coldest in the condenser).
The P-h diagram
Refrigeration uses the pressure–enthalpy diagram, with pressure on a logarithmic scale: evaporator and condenser are horizontal, the valve is vertical, and the heats and the work are read as horizontal lengths. Inside the dome the pressure fixes the temperature; to the right is the superheated vapor, where the compression ends.
Using the simulator
It is in Engineering → Thermodynamic cycles; the results are recomputed as you type. Everything is SI: absolute pressures in kPa, temperatures in °C for Rankine and refrigeration and in kelvin for Brayton, efficiencies in % (100 % = ideal).
- Cycle: first the family (Steam power, Gas turbines and propulsion, Refrigeration and heat pumps…) and below it the cycle: Rankine, Brayton or Refrigerator for this topic; each keeps its data. In Examples, «Load an example».
- Rankine: «Boiler pressure» and «Turbine inlet temperature» (or the box «Saturated vapor to the turbine (no superheat)»), «Condenser pressure» (saturated liquid leaves it), «Turbine (isentropic)», «Pump (isentropic)», «Net power (optional)» in MW and the box «With reheat», which opens «Reheat pressure» and «Reheat temperature» (it proposes the geometric mean of the pressures). The turbine efficiency applies to both turbines.
- Brayton: Air model «Variable specific heats» (air table) or «Cold-air standard» (asks for k = cₚ/cᵥ and cₚ); «Compressor inlet T₁», «Pressure P₁», «Pressure ratio rₚ», «Turbine inlet T₃»; «Compressor (isentropic)», «Turbine (isentropic)», «Regenerator (effectiveness)» (0 % = none) and «Net power (optional)».
- Refrigerator: the «Fluid» (any refrigerant of the tables); By pressures or By temperatures of saturation (switching converts the values); «Compressor (isentropic)», «Cooling capacity» in kW (empty = results per kg; tons × 3.517), «Superheat» and «Subcooling» in °C.
- Results: cards (efficiency with Carnot, net work, heats, exit quality, «Back work ratio», flow if a power or capacity is given; in refrigeration «Refrigeration COP», «Heat-pump COP», «Refrigerating effect», «Quality after the valve» and in kW and tons); Diagrams T-s (and P-h in refrigeration) with the real dome, thick dashed for the actual process and thin for the isentropic one; Cycle states (P, T, h, s, quality or , description); Step by step; and Detailed solution (PDF), with each state read and interpolated in the table, the balances and the checks.
- Warnings (⚠): exit quality below ~88 %, negative net work, useless regenerator (), discharge above 140 °C. An impossible value (turbine below boiling, a reheat that cools, superheat larger than the difference between condensing and evaporating, an efficiency outside 1–100 %) gives a message that names the field and explains why.
Common mistakes
- Applying the efficiency the wrong way: turbine ; compressor and pump .
- Finding the actual turbine exit with (that is the isentropic one) instead of with and .
- Forgetting in the reheat , or the work of the high-pressure turbine.
- Using °C in , in or in the Carnot COP.
- With variable specific heats, using instead of .
- Using a regenerator with , or computing from when there is one (it is from ).
- Taking after the valve: it is a mixture with .
- Confusing tons of refrigeration with kW, or mixing refrigerant tables with different references.
Worked examples
Example 1Ideal Rankine cycle
Solution
- State 1, saturated liquid at 75 kPa: °C, kJ/kg, m³/kg, kJ/kg·K.
- Pump: kJ/kg and kJ/kg.
- State 3: at 3 MPa water boils at 233.85 °C, so at 350 °C it is superheated vapor: kJ/kg, kJ/kg·K.
- State 4: lies between and at 75 kPa: and kJ/kg.
- , , and kJ/kg .
- %; %; Carnot: %.
Solve it in Simuveliq
- Steam power → Rankine, «Load an example» → Ideal Rankine: 3 MPa, 350 °C, 75 kPa.
- Cards: 26.02 % (Carnot 41.44 %), 710 kJ/kg, «Exit quality» 88.61 %, back work 0.4252 %. The step by step compares = 3.032 kJ/kg with = 3.034 kJ/kg.
Example 2Plant with reheat and real turbines
Solution
- State 1 (10 kPa, ): kJ/kg, m³/kg. Pump: kJ/kg (the equation of state gives 15.10: the liquid is slightly compressed); kJ/kg and kJ/kg.
- State 3: kJ/kg, . At 3 MPa, : superheated; interpolating, kJ/kg. kJ/kg (358.8 °C).
- State 5 (3 MPa, 600 °C): , . At 10 kPa: , ; kJ/kg and .
- kJ/kg; kJ/kg; kJ/kg and %.
- kg/s and MW (223.2 MW to the condenser).
- Without reheat: (below the erosion limit), % and kg/s. Reheat dries the steam, raises η by 2.4 points and saves 19 % of the flow.
Solve it in Simuveliq
- The button opens the case; by hand: 15000 kPa, 600 °C, 10 kPa, «Turbine (isentropic)» 88, «Pump (isentropic)» 90, «Net power (optional)» 150 and «With reheat» with 3000 kPa and 600 °C.
- Cards: 40.2 %, «Exit quality» 98.02 %, «Steam flow» 95.18 kg/s with 373.2 and 223.2 MW; six states in the table. Untick «With reheat»: 37.78 %, 117.6 kg/s and the warning «The quality at the turbine exit is 87.8 %…».
Example 3Ideal Brayton: air table versus cold-air standard
Solution
- At 300 K: kJ/kg, . gives K and kJ/kg.
- At 1300 K: kJ/kg, . gives K and kJ/kg.
- , , and kJ/kg: % and %.
- Cold air: , K, K, % and kJ/kg. It overestimates η by 2.3 points and gives an exhaust 53 K colder.
Solve it in Simuveliq
- Gas turbines and propulsion → Brayton, «Load an example» → Ideal Brayton: rp = 8, 300 K and 1300 K (variable specific heats): 42.55 %, «T₂ · T₄» 539.8 · 770.3 K, back work 40.24 %; the states table has the column.
- Press «Cold-air standard» in Air model: 44.8 %, 543.4 · 717.7 K and 340.6 kJ/kg.
Example 4Real gas turbine with a regenerator
Solution
- : K, kJ/kg; kJ/kg ( K).
- At 1400 K: kJ/kg, ; : K, ; kJ/kg ( K).
- , so the regenerator helps: kJ/kg ( K) and kJ/kg ( K).
- , , kJ/kg ( %). With the regenerator and %; without it and %.
- kg/s and MW (75.63 MW without the regenerator).
- With : K and K. The exhaust is colder than the compressed air: the regenerator cannot be used and η stays at 37.0 %.
Solve it in Simuveliq
- The button opens the case: «Variable specific heats», 300 K, 100 kPa, rₚ = 10, 1400 K, «Compressor (isentropic)» 85, «Turbine (isentropic)» 88, «Regenerator (effectiveness)» 75, «Net power (optional)» 25.
- Cards: 42.57 %, «T₂ · T₄» 621 · 864.5 K, back work 52.91 %, «Air flow» 85.35 kg/s with 58.72 MW. Regenerator at 0: 33.06 %. With rₚ = 25 the warning «With T₄ = 716.9 K ≤ T₂ = 808.1 K the regenerator cannot heat the compressor air: it is not used» appears.
Example 5Ideal R-134a refrigerator
Solution
- State 1, saturated vapor at 0.14 MPa: °C, kJ/kg, kJ/kg·K.
- State 2: 0.8 MPa with , superheated; interpolating, kJ/kg and °C.
- State 3, saturated liquid at 0.8 MPa: kJ/kg ; at 0.14 MPa, .
- , , kJ/kg; (heat pump: 4.97).
- kW (2.04 tons), kW and kW.
- Carnot between 254.39 K and 304.48 K: ; the cycle reaches 78 % of it (losses in the valve and in the superheated vapor cooled in the condenser).
Solve it in Simuveliq
- Refrigeration and heat pumps → Refrigerator, «Load an example» → Ideal R-134a between 0.14 and 0.8 MPa, 0.05 kg/s: «Refrigeration COP» 3.968 (Carnot 5.079), «Heat-pump COP» 4.968, T₂ = 38.98 °C, «Quality after the valve» 0.3225 and = 7.184 kW (2.043 tons).
- Type «Superheat» 10 and «Subcooling» 8 to see the red cycle of the P-h figure (COP 4.295).
Example 62-ton freezer with superheat and subcooling
Solution
- kW. Pressures: kPa and kPa.
- State 1: 132.7 kPa and −16 °C, superheated: kJ/kg, kJ/kg·K.
- Compressor: kJ/kg at 887.0 kPa with ; kJ/kg, kJ/kg and °C.
- State 3: 887.0 kPa and 30 °C, compressed liquid: kJ/kg (the equation of state gives 93.57) .
- and kJ/kg; kg/s, kW and kW.
- and ; Carnot between K and K: .
Solve it in Simuveliq
- The button opens the case: R-134a, By temperatures −20 and 35 °C, «Compressor (isentropic)» 82, «Superheat» 4, «Subcooling» 5 and «Cooling capacity» 7.0337 kW (2 × 3.51685).
- Cards: COP 3.01 (Carnot 5.59), «Heat-pump COP» 4.01, «Compressor work» 49.21 kJ/kg with T₂ = 55.65 °C and «Refrigerant flow» 0.04749 kg/s with 7.034 kW (2 tons) and 2.337 kW. The table describes state 1 as «Vapor superheated by 4 °C» and state 3 as «Liquid subcooled by 5 °C».