Learn › Engineering

Psychrometrics and the psychrometric chart

Psychrometrics studies moist air: how much water the air carries, at what temperature it condenses and how much energy it takes to cool it, dry it or humidify it. It is the basis of air conditioning, drying, cooling towers and condensation on walls, windows and ducts. This topic derives every property of moist air from two ideal gases, explains how the psychrometric chart is built and read, goes through the air-conditioning processes (heating, cooling and dehumidifying, humidifying, evaporative cooling, mixing) and the sensible and latent loads of a room, and shows how to solve all of it with the site's Psychrometric calculator.

Moist air: dry air plus water vapor

Atmospheric air is a mixture of dry air (nitrogen, oxygen, argon, carbon dioxide…, of almost fixed composition) and a variable amount of water vapor. In psychrometrics dry air is treated as a single gas, of molar mass g/mol, and the vapor as another, of g/mol. Their gas constants are J/(kg·K) and J/(kg·K).

Between −20 and 50 °C and at pressures near atmospheric, both behave as ideal gases: the vapor pressure is a few kPa, far from the pressures at which the vapor stops being ideal. By Dalton's law, each gas fills the whole volume at the temperature of the mixture, as if it were alone, and exerts its partial pressure; the total pressure is the sum:

+=dry airma , pa water vapormv , pv moist airP = pa + pv the same volume V and the same temperature T
Dalton's law: dry air and vapor fill the same volume at the same temperature; each exerts its partial pressure and that of moist air is the sum.

In air-conditioning processes water evaporates or condenses, but the dry air entering a device is the same that leaves it. That is why every property of moist air (humidity, enthalpy, volume) is given per kilogram of dry air: one kg of dry air with whatever vapor it carries. It is the convention of the psychrometric chart and of the tool.

The tool computes the vapor and saturation with IAPWS-95 (the equation of «Thermodynamic tables») and dry air as an ideal gas with its . It does not apply the small «enhancement factor» that corrects for the interaction between air and vapor in real air: its humidity ratio differs from the ASHRAE tables by less than 0.5 %.

Saturation pressure: how much vapor fits

The partial pressure of the vapor cannot exceed the saturation pressure of water at the air temperature: the pressure of vapor in equilibrium with liquid water (or with ice, below 0.01 °C). If more vapor is added, or if the air is cooled until , the excess condenses into droplets (dew, fog) or frost. depends only on temperature: air does not «absorb» or «hold» the vapor; dry air only shares the volume.

−20−10010203040012345678T (°C)pressure (kPa)pv = 1.493pws = 2.986Tdp = 12.95 °Cover ice (IAPWS R14-08)over liquid water (IAPWS-95)supersaturated: the excess condensesunsaturated
Saturation pressure of water with the tool's equations: over liquid water (IAPWS-95) and, below the triple point (0.01 °C, 0.6117 kPa), over ice (IAPWS R14-08). The air of an office at 24 °C with kPa lies below the curve: its relative humidity is = 50 % (vertical) and, cooled at constant , it saturates at 12.95 °C, its dew point (horizontal).

The curve rises very fast: it almost doubles every 10 °C (1.228 kPa at 10 °C, 2.339 kPa at 20 °C and 4.247 kPa at 30 °C). That is why warm air can carry much more water than cold air, and why summer air cooled in a coil gives off water. The table gives the tool's values and the saturation humidity ratio (next section) at sea level:

T (°C) (kPa) at 101.325 kPa (g/kg)over
−200.10320.6344ice
−100.25991.599ice
0.01 (triple point)0.61173.777both phases
50.87265.403liquid
101.2287.631liquid
151.70610.65liquid
202.33914.70liquid
253.17020.09liquid
304.24727.21liquid
355.62936.58liquid
407.38548.89liquid
5012.3586.34liquid

Humidity ratio ω

The humidity ratio is the mass of vapor per unit mass of dry air. It follows from the two ideal-gas equations by dividing one by the other, since the volume and the temperature are the same:

The ratio is the «0.622» of the formulas (the tool uses 0.62196; with 0.622 the fourth digit of ω may change). The other way round, the vapor pressure follows from ω and the total pressure, and with instead of comes the saturation humidity ratio, the largest at that temperature and pressure:

ω is given in kg/kg, in g/kg (the usual: 9.301 g/kg in the office) or, in US units, in grains per pound: 1 lb = 7000 gr, so 1 g/kg = 7 gr/lb. As long as no water is added or removed, ω does not change when the air is heated or cooled: it is the vertical coordinate of the chart.

Do not confuse ω with the specific humidity , the one used in meteorology: with ω = 9.301 g/kg it gives 9.215 g/kg.

Relative humidity φ and degree of saturation μ

Relative humidity compares the vapor pressure with the largest possible at the same temperature, and the degree of saturation compares the humidity ratios:

The second equality comes from substituting ω and . Since , μ is slightly less than φ (in the office, μ = 49.25 % with φ = 50 %); both are 0 in dry air and 100 % at saturation. φ is what hygrometers measure and what the body feels: with high φ, sweat evaporates poorly.

φ depends strongly on temperature even if the air neither gains nor loses water. Winter outdoor air at 5 °C and 80 %, heated to 22 °C, keeps its ω = 4.315 g/kg, but its relative humidity falls to 26.39 % (example 4): that is why heating dries indoor air. Conversely, air being cooled rises in relative humidity until it reaches 100 %.

Dew point and frost point

If the air is cooled at constant pressure without removing water, ω and do not change, but falls. The temperature at which equals is the dew point : there the air becomes saturated and, cooled further, the vapor condenses.

The dew point depends only on , that is, on ω and P: it measures the amount of water, not the temperature. By hand, look up in the table and interpolate: in the office, kPa lies between 1.403 kPa (12 °C) and 1.498 kPa (13 °C), and °C. A surface colder than the dew point gets wet: the cold glass that «sweats», windows in winter, an uninsulated cold-water pipe, the coil that dehumidifies.

Below the triple point ( kPa) the vapor turns not into liquid but directly into ice: the saturation temperature is the frost point, with the sublimation pressure of ice (IAPWS R14-08). The tool says so on its card: with 20 °C and 20 %, kPa and the «Frost point (over ice)» card reads −3.206 °C.

Adiabatic saturation and wet-bulb temperature

Measuring ω directly is hard; measuring temperatures is easy. The adiabatic saturator is the ideal experiment that links them: a long insulated channel where the air (state 1) flows over water and keeps picking up moisture until it leaves saturated (state 2) at a temperature . The water that evaporates is made up at that same temperature . Since no heat enters, the water evaporates at the expense of the air's sensible heat, and the air cools.

1: T1 , ω1 2: T2 , ωs2 (saturated)insulated: no heat entersmake-up water at T2 adiabatic saturatordry bulbwet bulbwickmoving airpsychrometer
Left: adiabatic saturator. Right: psychrometer, with a dry thermometer and one with its bulb in a wet wick; the air must move over the wick.

Water and energy balance per kg of dry air (steady flow, no heat or work): the air leaves with because it received kg of water at , with its liquid enthalpy :

With (enthalpy section) is solved for; the second, approximate form uses and :

It is exactly the equation the tool uses. , the adiabatic saturation temperature, depends only on state 1 (and on P): it is a property of moist air, the thermodynamic wet-bulb temperature . For a given state it is found by trying values of until the equation gives its ω (the tool does it by bisection).

The psychrometer

In practice a psychrometer is used: two thermometers, one dry bulb (the air temperature) and one with its bulb wrapped in a wet wick. The water in the wick evaporates, the wick cools and receives heat from the air by convection; it settles when that heat equals the heat taken by evaporation. That equilibrium temperature depends on heat and mass transfer, not on the saturator balance, but for air and water both nearly coincide: the ratio of the heat to the mass transfer coefficient is very close to the of moist air (the Lewis relation is almost 1). That is why the wet thermometer reading, with the air moving (the psychrometer is whirled or ventilated) and shielded from radiation, is a good measure of the thermodynamic wet bulb.

A line of constant wet bulb is the path of the air in an adiabatic saturator. It nearly coincides with a line of constant enthalpy, because the water added brings little enthalpy, . Along the 20 °C line, computed with the tool, h falls only 0.7 kJ/kg from 20 to 40 °C:

Dry bulb (°C)ω (g/kg)h (kJ/kg dry air)
2014.7057.38
2512.6057.20
3010.5357.03
358.46256.85
406.41256.68
The tool gives the wet bulb from 0.01 °C (with liquid water in the wick). If it would come out below, the card says «below 0 °C»: for instance with 2 °C and 30 %, whose frost point is −12.28 °C.

Enthalpy of moist air

The enthalpy of the mixture is the sum of those of its two components, each with its mass. Per kg of dry air:

References have to be chosen, because only differences matter. Those of ASHRAE, used by the tool, are dry air at 0 °C () and liquid water at the triple point ( at 0.01 °C). The vapor is taken as an ideal gas: its enthalpy depends only on T and is that of saturated vapor at that temperature, ; at 0.01 °C it is 2500.9 kJ/kg, the heat of vaporization of water at that temperature.

With the tool's values, kJ/(kg·K) at 25 °C and grows 1.815 kJ/kg per degree between 0.01 and 40 °C, so a very handy approximate formula, with T in °C, is:

The first term is the sensible heat of the dry air; is the latent heat, the energy it took to evaporate that water, given back if it condenses; the last one, the sensible heat of the vapor. Against the exact one, the approximation is off by hundredths of a kJ/kg:

Stateω (g/kg)exact h (kJ/kg)approximate h
24 °C, 50 %9.30147.7747.78
30 °C, 60 %16.0471.1371.14
5 °C, 80 %4.31515.8515.85
38 °C, 20 %8.25159.3759.38

In US units the tool uses the ASHRAE inch-pound reference, dry air from 0 °F: h in Btu/lb of dry air is , with kJ/kg. That is why the US enthalpy is not the SI one divided by 2.326: the office has 47.77 kJ/kg and 28.21 Btu/lb. Enthalpy differences (the heats of the processes) do convert with 1 Btu/lb = 2.326 kJ/kg.

Specific volume and density

The specific volume of the chart is the volume of moist air that contains 1 kg of dry air. Since the dry air fills the whole volume at its partial pressure:

In the office, m³/kg of dry air and ρ = 1.181 kg/m³. Dry air at the same temperature and pressure weighs 1.188 kg/m³: moist air is lighter, because each water molecule (18 g/mol) takes the place of an air molecule (29 g/mol).

The specific volume converts the volume flow, which is what a fan moves, into the dry-air flow, which is what goes into the balances: . The tool does it with the v of state 1.

Altitude and barometric pressure

Every formula contains the total pressure P. At higher altitude the pressure falls; with the standard atmosphere (ISO 2533, troposphere), the one the tool uses:

At 2600 m, P = 73.75 kPa. With the same temperature and relative humidity, is the same, but grows because the denominator is smaller: there is less dry air with the same amount of vapor. The dew point does not change (it depends only on ), the wet bulb falls a little and the specific volume grows a lot. For 25 °C and 50 %:

Altitude (m)P (kPa)ω (g/kg)Wet bulb (°C)h (kJ/kg)v (m³/kg)
0101.339.88317.8950.270.8581
100089.8711.1717.6053.540.9694
200079.5012.6517.3157.321.098
260073.7513.6617.1459.891.186
300070.1114.3917.0361.741.249
051015202530354005101520253035Dry-bulb temperature (°C)ω (g/kg dry air)0 m2600 mφ = 60 %
Saturation and φ = 60 % at sea level (0 m, 101.33 kPa, in blue) and at 2600 m (73.75 kPa, in orange). The same air (18 °C, 60 %) has ω = 7.698 g/kg below and 10.63 g/kg above, with the same dew point, 10.13 °C: the saturation curve rises when the pressure falls.
Use the chart for the local pressure: the tool draws it at the chosen pressure («Psychrometric chart at 73.749 kPa» in example 3). A sea-level chart used at 2600 m gives an ω 28 % too low.

How the psychrometric chart is built and read

The psychrometric chart draws all these relations for one pressure. In the tool's (and in almost every one) the horizontal axis is the dry-bulb temperature and the vertical one, on the right, the humidity ratio ω. Each point is a state: any two properties fix it, and the rest are read on the lines through it.

Saturation and relative humidity

The saturation curve is , the edge of the chart: to its left no moist air is possible. The curves of constant relative humidity come from and are almost proportional to the saturation curve (the 50 % one runs at about half height). The tool puts a mark every 1 °C on the saturation curve: in a saturated state the dry bulb, the wet bulb and the dew point coincide.

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)20 %40 %60 %80 %saturation: φ = 100 %
Saturation and relative humidity every 10 % at 101.325 kPa, computed with the tool's equations. To the left of the saturation curve no moist air is possible.

Wet bulb and enthalpy

The lines of constant wet bulb come from the saturator equation: nearly exact straight lines falling to the right from saturation, where . Those of constant enthalpy, , are almost parallel: in the office the wet-bulb line falls 0.413 g/kg per degree and the enthalpy line, 0.401. So as not to confuse them, the enthalpy scale is outside the saturation curve: the tool extends each enthalpy line 2.5 °C beyond the curve and writes its value there.

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)30 kJ/kg60 kJ/kg90 kJ/kg5 °C15 °C25 °Cwet bulbenthalpy (kJ/kg)
Lines of constant wet bulb (dashed) and constant enthalpy (solid). The 25 °C wet-bulb line runs almost along the 76 kJ/kg one, not drawn.

Specific volume

The lines of constant specific volume, , are much steeper; the tool draws one every 0.01 m³/kg. They meet the ω = 0 axis at the temperature of dry air with that volume, .

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)0.800.820.840.860.88v (m³/kg dry air)
Lines of constant specific volume every 0.02 m³/kg of dry air at 101.325 kPa.

Reading a state

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)ORBH50 %
Reading the office state, O (24 °C, 50 %, ω = 9.301 g/kg on the right axis): R, the dew point, 12.95 °C, at constant ω up to saturation; B, the wet bulb, 17.06 °C, along its sloping line up to saturation; H, the enthalpy, 47.77 kJ/kg, on its scale, 2.5 °C outside the curve.
  • Dry bulb: the vertical down to the horizontal axis (24 °C).
  • Humidity ratio: the horizontal to the right axis (9.301 g/kg).
  • Relative humidity: the curve through the point (50 %), or interpolating between two.
  • Dew point: the horizontal to the left up to saturation (12.95 °C).
  • Wet bulb: the wet-bulb line through the point, up to saturation (17.06 °C).
  • Enthalpy: the h line through the point, read on its scale (47.77 kJ/kg).
  • Specific volume: interpolating between the 0.84 and 0.86 lines (0.8544 m³/kg).

On a printed chart three digits at most can be read; the tool gives four and is more exact than any reading, but drawing the process on the chart helps to see whether it makes sense.

The sensible heat ratio protractor

In a corner of the chart there is a protractor: a quarter circle with radii marked with the sensible heat ratio SHR (sensible heat / total heat). A process with sensible heat and latent heat has on the chart the slope:

The tool computes it at 24 °C ( kJ/(kg·K) and kJ/kg) and draws each radius in pixels, because the angle depends on the scales of each chart. To use it, draw through the room state a parallel to the radius of the SHR of its load: the supply air must lie on that line (example 8). SHR = 1 is a horizontal (sensible heat only) and SHR = 0, a vertical (latent only).

LineEquationOn the tool's chart
Saturation (φ = 100 %)thick curve, with a mark every 1 °C
Relative humidityevery 10 %
Wet bulbthe adiabatic saturator'sdashed every 1 °C, numbered every 5 °C
Enthalpyevery 10 kJ/kg, scale 2.5 °C outside saturation
Specific volumeevery 0.01 m³/kg
Protractor (SHR)upper left, at 24 °C

Air-conditioning processes

An air-handling unit chains several processes: it mixes the return air with outdoor air, filters it, cools and dehumidifies it, reheats it if needed and supplies it to the room, where it takes up the loads and returns.

mixingcooling coilfanfilterheating coilcondensateroomQs + Ql outdoorreturn airexhaust123456
Air-handling unit: 1 outdoor, 2 return, 3 mixture, 4 after the cooling coil (almost saturated), 5 after the heating coil, 6 supply to the room, which receives the sensible and latent loads (people, sun, equipment…).

Each device is a control volume in steady flow. With the dry-air flow (the same at inlet and outlet), the water entering (or leaving, with a minus sign) with its enthalpy , and the heat received by the air:

Per kg of dry air, . The water term is usually small with liquid water and large with steam. The tool gives split exactly into a sensible part (changing T at fixed ω) and a latent part (changing ω at the final temperature):

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)123456O
Directions of the processes from one state O (24 °C, 50 %), computed: 1 heating (constant ω); 2 cooling without condensing; 3 humidifying with steam at 100 °C, almost vertical; 4 evaporative cooling, along the wet-bulb line; 5 cooling and dehumidifying and 6 heating and humidifying, both with SHR = 0.6.
ProcessOn the chartωφhSHR
Sensible heatinghorizontal to the rightsamefallsrises1
Sensible cooling (above the dew point)horizontal to the leftsamerisesfalls1
Cooling and dehumidifyingdown to the left, toward saturationfallsrisesfallsbetween 0 and 1
Steam humidificationalmost vertical, upwardrisesrisesrisesnear 0
Evaporative coolingalong the wet-bulb line, up to the leftrisesrisesalmost the samemeaningless (total ≈ 0)
Heating and humidifyingup to the rightrisesdependsrisesbetween 0 and 1
Adiabatic mixingon the line between the two streamsin between—in between—

Sensible heating and cooling

An electric heater or a hot-water coil heats the air without changing its ω: the process is a horizontal to the right. The heat is , all of it sensible. The relative humidity falls (example 4: from 80 to 26.39 %). Cooling without condensing is the horizontal to the left, possible as long as the cold surface stays above the dew point.

Cooling with dehumidification

To remove water, the coil surface must be colder than the dew point of the air. The air touching the cold fins is cooled below its dew point and condenses; the air passing between them is cooled less, and at the outlet they mix: the air leaves cold, almost saturated and with less ω. Ideally, the air is first cooled at constant ω down to its dew point and then runs down the saturation curve; the real outlet state lies slightly to the right of that curve.

The line joining inlet and outlet, extended, meets the saturation curve at the apparatus dew point (ADP): the effective temperature of the coil surface. In example 5 (30 °C, 60 % → 14 °C, 95 %) the line has a slope of 0.4112 g/kg per degree and meets saturation at 11.46 °C. The tool does not compute it: it is read by extending line 1 → 2 on its chart, or found by trying temperatures until the ω of the line equals the saturation one.

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)−6.579 g/kg12RA
Example 5 on the chart: inlet 1 (30 °C, 60 %, dew point 21.39 °C) and outlet 2 (14 °C, 95 %). The coil line 1 → 2 (red) is extended to the apparatus dew point, A (11.46 °C). The ideal path (dashed): cooling at constant ω to the dew point, R, where condensing starts, and down along saturation. On the right, the 6.579 g/kg that condense.

The condensate also enters the energy balance of the coil: it leaves at a temperature near that of the cold air and takes its enthalpy, . In example 5 that is 0.387 kJ/kg against 33.16 kJ/kg of : the heat removed by the coil is 32.77 kJ/kg, 1.2 % less than .

Humidifying with steam and with water

Adding water without heat, the energy balance says : the direction on the chart depends on the enthalpy of the water added. Starting from the heated air of example 4 (22 °C, 4.315 g/kg) and adding 4 g/kg:

  • With saturated steam at 100 °C ( kJ/kg): kJ/kg and the air leaves at 22.53 °C with 48.93 %: almost a vertical, the temperature rising barely half a degree.
  • With water sprayed at 20 °C ( kJ/kg): kJ/kg and the air leaves at 12.36 °C with 93.06 %: evaporating that water cools the air almost 10 °C.

That is why water humidifiers go after a heating coil (or the water is heated), while steam humidifiers hardly change the temperature.

Evaporative cooling

If the water is recirculated, it takes the wet-bulb temperature of the air, and the process follows the line of constant wet bulb: the air cools and gains moisture with almost no change in enthalpy. The drier the air, the more it cools, and the limit is the wet bulb. The saturation effectiveness of an evaporative pad compares how much it cools with that limit:

With air at 38 °C and a 21 °C wet bulb, a pad of effectiveness 0.8 brings it to 38 − 0.8 · 17 = 24.4 °C (example 6). It works in dry climates; in a humid one the wet bulb is close to the dry bulb, it hardly cools and the air leaves very humid.

Adiabatic mixing of two streams

Mixing outdoor air with return air is the most common step in an air-handling unit. With no heat or work, the dry-air, water and energy balances are:

Eliminating from the last two:

The two ratios being equal means that the (h, ω) points of the three streams lie on a straight line, and that point 3 divides it into parts inversely proportional to the dry-air flows (the lever rule): the mixture lies closer to the larger stream. Since the h lines of the chart are nearly straight and parallel, the mixture also falls on the line joining 1 and 2 on the T–ω chart, with an error of hundredths of a degree: in example 7 the line passes through 25.94 °C at the ω of the mixture, and the exact temperature is 25.96 °C. If both streams are close to saturation, the line may pass above the curve (which is convex): the mixture would hold more vapor than at saturation, and fog forms.

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)123
Example 7: the mixture 3 (25.96 °C, 11.05 g/kg) on the line between outdoor air 1 (32 °C, 55 %; 1352 kg/h of dry air) and return air 2 (24 °C, 50 %; 4213 kg/h), closer to the return air, which carries more dry air. In ω, the stretch 1–3 is 3.116 times 3–2: the inverse ratio of the dry-air flows, 4213/1352.

Room loads: sensible, latent and SHR

A room receives sensible heat (sun, people, equipment, lighting, walls) and latent heat (the vapor from people, cooking, infiltration). The supply air enters colder and drier and leaves at the room state; on the way it takes up both loads (su: supply, r: room):

It is the same split as the tool's, with state 1 the supply and 2 the room. The SHR fixes the room line on the chart, and the supply air must lie on it; once its temperature is chosen, its ω and the flow are fixed. With 12 kW sensible and 3 kW latent (SHR = 0.8) and supply air at 14 °C for a room at 24 °C and 50 %, 1.177 kg/s of dry air with ω = 8.299 g/kg are needed (example 8).

0510152025303540051015202530Dry-bulb temperature (°C)ω (g/kg dry air)LI1.00.80.50.30.2sensible heat ratio
Example 8: the room line with SHR = 0.8 (red) passes through the room, L (24 °C, 50 %), and the supply, I (14 °C, 8.299 g/kg), and is almost parallel to the 0.8 radius of the protractor, drawn by the tool at 24 °C. It meets saturation at 10.62 °C: no colder supply is possible along that line.

SI and US units

The «SI» and «US» buttons in the header change every unit of the tool and convert the data already typed. The equivalences it uses:

QuantitySIUSConversion
Temperature°C°F
Temperature differenceK°F1 K = 1.8 °F
PressurekPapsia1 psi = 6.894757 kPa
Altitudemft1 ft = 0.3048 m
Humidity ratiog/kggr/lb1 g/kg = 7 gr/lb
EnthalpykJ/kg dry airBtu/lb dry air (dry air from 0 °F)
Heat per kgkJ/kgBtu/lb1 Btu/lb = 2.326 kJ/kg
Specific volumem³/kgft³/lb1 m³/kg = 16.018 ft³/lb
Densitykg/m³lb/ft³1 lb/ft³ = 16.018 kg/m³
Air flowm³/hcfm1 cfm = 1.699 m³/h
PowerkWBtu/h1 kW = 3412.14 Btu/h
Water flowkg/hlb/h1 lb = 0.45359 kg

The office of example 1 in US units: 75.2 °F and 50 % at 14.696 psia give ω = 65.11 gr/lb, h = 28.21 Btu/lb, wet bulb 62.71 °F, dew point 55.3 °F and v = 13.69 ft³/lb. The chart is always drawn in SI.

Using the simulator

It is in Engineering → Thermodynamics and fluids → Psychrometric calculator. The «Data» card is on the left; on the right, the results and the chart, recomputed with every keystroke.

  • Examples: the dropdown («Choose…») brings five cases; they are examples 1 to 5 of this topic.
  • 1. Air pressure: «Altitude (standard atmosphere)» with «Altitude above sea level» in m (or ft), or «Pressure» with «Barometric pressure» in kPa (or psia). The pressure must be between 30 and 200 kPa.
  • 2. Air state: «Dry-bulb temperature» (0 to 90 °C) and a «Second property» to choose: «Relative humidity φ» (in %), «Wet-bulb temperature», «Dew point», «Humidity ratio ω» (in g/kg) or «Enthalpy h» (in kJ/kg). Changing the property empties its field.
  • Second state: the «Second state: the process from 1 to 2 (heating, cooling, humidifying…)» box opens «3. State 2», with the same fields, and «Air flow at state 1 (optional)» in m³/h (or cfm).

With one state there is one card per property; with two, a «Property · State 1 · State 2» table and the «Process from 1 to 2» block:

CardWhat it is
«Dry bulb», «Relative humidity φ»the data or what follows from them
«Wet bulb»the thermodynamic one (adiabatic saturation); «below 0 °C» if it would be under 0.01 °C
«Dew point» or «Frost point (over ice)»over ice when is below that of the triple point
«Humidity ratio ω», «Enthalpy h», «Specific volume v»per kg of dry air
«Moist-air density», per m³ of moist air
«Vapor pressure p_v», «Saturation pressure at T» is their ratio
«Degree of saturation μ», «Saturation ω at T»
«Sensible heat», «Latent heat», «Total heat Δh»the exact split of , per kg of dry air
«Sensible heat ratio», «Water added (+) or condensed (−)», «ΔT»SHR = sensible/total; ;
«Dry air», «Sensible power», «Latent power», «Total power», «Condensate» or «Water to humidify»with the flow: and each heat times

The «Psychrometric chart at … kPa» card draws the complete chart at the chosen pressure, from 0 to 50 °C, with the state («State») or states 1 and 2 and the line between them; below are the legend and how to read a state. The chart is always in SI, even if the data are in US units. The «Report» button in the header saves the results and the chart.

The messages and what to do

Message (summarized)What it means and what to do
«The dry-bulb temperature must be between 0 and 90 °C…»The calculation uses liquid water; air below freezing is not computed (its frost point is).
«The pressure must be between 30 and 200 kPa…»Almost always the unit: kPa, not Pa or bar; or an impossible altitude.
«At that pressure water boils below that temperature…»With low pressure and high temperature there is no moist air: lower T or raise P.
«The relative humidity must be between 0 and 100 %.»It goes in %, not as a fraction: 50, not 0.5.
«The wet bulb must be between 0.01 °C and the dry-bulb temperature.»The wet bulb is never above the dry bulb.
«The dew point cannot be higher than the dry-bulb temperature.»Check which is which.
«…more vapor than at saturation (over 100 %)…»ω or h too high for that temperature; ω goes in g/kg.
«With those data the humidity ratio would be negative…»h or the wet bulb too low: not even dry air gets there.

Common mistakes

  • Using the sea-level chart at altitude: at 2600 m, ω comes out 28 % too low.
  • Typing the relative humidity as a fraction (0.5) instead of % (50), or ω in kg/kg instead of g/kg.
  • Giving h per kg of moist air: everything is per kg of dry air, and the dry-air flow is , not (that is moist air).
  • Believing that heating the air dries it: ω does not change, only φ falls.
  • Confusing wet bulb and dew point: the dew point is at constant ω (horizontal) and the wet bulb at almost constant h (sloping line); always .
  • Forgetting that to dehumidify the coil surface must be below the dew point of the inlet (21.39 °C in example 5).
  • Mixing enthalpies with different references (SI and US, or another table): differences of h do not depend on the reference, the values do.
  • Averaging the mixture with the volume flows: ω and h are averaged with the dry-air flows.

Worked examples

To solve them by hand, the formulas above and these values of the tool, at each degree, are enough (interpolate between degrees):

T (°C) (kPa) (kJ/kg) (kJ/kg) (kJ/kg)
50.87265.0192510.121.02
121.40312.052522.950.41
131.49813.052524.754.60
141.59914.062526.558.79
151.70615.062528.362.98
182.06518.072533.875.54
202.33920.082537.483.91
212.48821.092539.388.10
222.64522.092541.192.28
242.98624.102544.7100.6
253.17025.102546.5104.8
304.24730.132555.5125.7
324.76032.142559.2134.1
386.63338.172569.9159.2

Example 1The properties of the air in an office

An office at sea level (101.325 kPa) has its air at 24 °C and 50 % relative humidity. Find the vapor pressure, the humidity ratio, the degree of saturation, the enthalpy, the specific volume, the density, the dew point and the wet bulb.

Solution

  1. From the table, = 2.986 kPa at 24 °C, so kPa.
  2. kg/kg = 9.301 g/kg. With g/kg, = 49.25 %.
  3. kJ/kg of dry air.
  4. m³/kg and kg/m³.
  5. Dew point: 1.493 kPa lies between 12 °C (1.403) and 13 °C (1.498): °C. The wet bulb comes from trying values in the saturator equation: with °C it gives ω = 9.30 g/kg, that of the air.
= 1.493 kPa, ω = 9.301 g/kg, μ = 49.25 %, h = 47.77 kJ/kg, v = 0.8544 m³/kg, ρ = 1.181 kg/m³, dew point 12.95 °C and wet bulb 17.06 °C.

Solve it in Simuveliq

  1. In Engineering → Psychrometric calculator, «Examples» → Office: 24 °C and 50 % relative humidity. The pressure stays at «Altitude (standard atmosphere)» with 0 m: 101.33 kPa.
  2. The cards give «Vapor pressure p_v» 1.493 kPa, «Humidity ratio ω» 9.301 g/kg, «Degree of saturation μ» 49.25 %, «Enthalpy h» 47.77 kJ/kg, «Specific volume v» 0.8544, «Moist-air density» 1.181, «Dew point» 12.95 °C and «Wet bulb» 17.06 °C.
  3. Press «US» in the header: 75.2 °F, ω = 65.11 gr/lb, h = 28.21 Btu/lb and dew point 55.3 °F. Go back to «SI».

Example 2From the psychrometer to the humidity

A ventilated psychrometer reads 30 °C on the dry bulb and 20 °C on the wet bulb, at sea level. Find the humidity ratio, the relative humidity, the dew point and the enthalpy.

Solution

  1. The wet bulb is the outlet of the saturator: at 20 °C, kPa and g/kg.
  2. Saturator equation with the table: , that is ω = 10.53 g/kg.
  3. kPa and = 39.71 %.
  4. Dew point: 1.686 kPa between 14 °C (1.599) and 15 °C (1.706) gives °C. Enthalpy: kJ/kg.
  5. Note the order: dew point 14.82 °C < wet bulb 20 °C < dry bulb 30 °C. The three coincide only in saturated air.
ω = 10.53 g/kg, φ = 39.71 %, dew point 14.82 °C and h = 57.03 kJ/kg.

Solve it in Simuveliq

  1. «Examples» → Psychrometer: dry bulb 30 °C, wet bulb 20 °C. The «Second property» is «Wet-bulb temperature».
  2. Cards: «Humidity ratio ω» 10.53 g/kg, «Relative humidity φ» 39.71 %, «Dew point» 14.82 °C and «Enthalpy h» 57.03 kJ/kg.
  3. Try other wet bulbs: with 30 (equal to the dry bulb) φ = 100 %; with 10 the warning «With those data the humidity ratio would be negative» appears: at 30 °C not even completely dry air has a wet bulb below 10.52 °C.

Example 3The same air at 2600 m

In a city at 2600 m altitude the air is at 18 °C and 60 %. With the standard atmosphere, find the pressure, the humidity ratio, the specific volume, the density and the wet bulb, and compare them with the same air at sea level.

Solution

  1. kPa.
  2. kPa, the same as at sea level: it depends only on T and φ.
  3. g/kg; at sea level, g/kg: 38 % more at altitude.
  4. m³/kg (0.8350 below) and ρ = 0.8768 kg/m³ (1.207 below). The dew point is 10.13 °C in both places; the wet bulb falls from 13.41 to 12.84 °C.
  5. A fan moving the same volume flow carries 28 % less dry air at altitude (0.8350/1.153 = 0.724): equipment is sized by mass.
P = 73.75 kPa, ω = 10.63 g/kg (7.698 at sea level), v = 1.153 m³/kg, ρ = 0.8768 kg/m³, wet bulb 12.84 °C; dew point 10.13 °C in both cases.

Solve it in Simuveliq

  1. «Examples» → At 2600 m altitude: 18 °C and 60 %. Above the results it says «standard atmosphere at 2600 m» with 73.749 kPa, and the chart is the «Psychrometric chart at 73.749 kPa».
  2. Cards: «Humidity ratio ω» 10.63 g/kg, «Specific volume v» 1.153, «Moist-air density» 0.8768, «Wet bulb» 12.84 °C and «Dew point» 10.13 °C.
  3. Change «Altitude above sea level» to 0: ω = 7.698 g/kg, v = 0.835, wet bulb 13.41 °C; the dew point does not move.

Example 4Winter heating

A unit takes 500 m³/h of outdoor air at 5 °C and 80 % and heats it to 22 °C without humidifying. Find the heat per kg of dry air, the power and the relative humidity at the outlet.

Solution

  1. State 1: kPa, g/kg and kJ/kg.
  2. On heating, ω does not change: kJ/kg.
  3. kJ/kg, all sensible (SHR = 1). With the approximate formula, kJ/kg.
  4. kg/s = 630.2 kg/h, and kW.
  5. Outlet: = 26.39 %. The dew point stays at 1.84 °C: the air has not dried, it is only warmer.
q = 17.21 kJ/kg and 3.012 kW with 630.2 kg/h of dry air; φ falls from 80 % to 26.39 %.

Solve it in Simuveliq

  1. «Examples» → Winter heating (constant ω): 5 °C, 80 % → 22 °C. The «Second state: the process from 1 to 2 (heating, cooling, humidifying…)» box is checked, and state 2 has «Humidity ratio ω» = 4.315 g/kg, that of state 1.
  2. In «Process from 1 to 2»: «Sensible heat» 17.2 kJ/kg, «Latent heat» 0.001059 (zero but for the rounding of 4.315), «Total heat Δh» 17.21 and «Sensible heat ratio» 1; with 500 in «Air flow at state 1 (optional)», «Dry air» 630.2 kg/h and «Total power» 3.012 kW.
  3. In the table, «Relative humidity φ» goes from 80 to 26.39 % and the «Dew point» stays at 1.842 and 1.844 °C. On the chart, the process is a horizontal.

Example 5Cooling and dehumidifying coil

A coil cools 2000 m³/h of air from 30 °C and 60 % to 14 °C and 95 %, at sea level. Find the sensible, latent and total heat per kg of dry air, the sensible heat ratio, the cooling power and the water condensed. Where is the apparatus dew point?

Solution

  1. Inlet: kPa, g/kg, kJ/kg and m³/kg. Its dew point is 21.39 °C: a colder surface condenses.
  2. Outlet: kPa, g/kg and kJ/kg.
  3. Split: ; sensible , latent , total −33.16 kJ/kg, and SHR = 16.54/33.16 = 0.499.
  4. kg/s (2270 kg/h): kW (−10.43 sensible and −10.48 latent). Water condensed: kg/h.
  5. With the condensate leaving at 14 °C ( kJ/kg), the coil removes kJ/kg, 20.67 kW. Line 1 → 2, with a slope of 0.4112 g/kg per degree, meets saturation at the apparatus dew point: 11.46 °C.
Sensible −16.54, latent −16.62 and total −33.16 kJ/kg; SHR = 0.499; 20.91 kW (20.67 kW counting the condensate); 14.94 kg/h of water; apparatus dew point 11.46 °C.

Solve it in Simuveliq

  1. «Examples» → Cooling and dehumidifying coil: 30 °C, 60 % → 14 °C, 95 %, with 2000 m³/h in «Air flow at state 1 (optional)».
  2. «Process from 1 to 2»: «Sensible heat» −16.54, «Latent heat» −16.62, «Total heat Δh» −33.16 kJ/kg, «Sensible heat ratio» 0.499 and «Water added (+) or condensed (−)» −6.579 g/kg; «Dry air» 2270 kg/h, «Total power» −20.91 kW and «Condensate» 14.94 kg/h.
  3. To check the apparatus dew point, type in state 2 11.46 °C with «Relative humidity φ» 100: ω = 8.422 g/kg, the same the line 1 → 2 gives at that temperature.

Example 6Evaporative cooler in a dry climate

Outdoor air at 38 °C with a 21 °C wet bulb, at sea level, goes through an evaporative pad of saturation effectiveness 0.8, with the water recirculating. Find the outlet temperature and relative humidity and the water evaporated with 3000 m³/h.

Solution

  1. The recirculated water is at the wet bulb and the process follows the 21 °C line: °C, with the same wet bulb.
  2. Inlet, with the saturator equation: = 2.488 kPa at 21 °C, g/kg and g/kg; = 20.79 %.
  3. Outlet, the same equation with and (interpolating): g/kg and = 74.10 %.
  4. kg/s, and kg/h of water evaporate.
  5. The enthalpy hardly changes: kJ/kg, exactly that of the water added, . The sensible (−13.88 kJ/kg) and latent (+14.38) heats almost cancel, and that is why their ratio (SHR) means nothing here.
It leaves at 24.4 °C and 74.10 %, with ω from 8.581 to 14.23 g/kg; 18.96 kg/h of water evaporate.

Solve it in Simuveliq

  1. The button opens both states: 1 with 38 °C and «Wet-bulb temperature» 21, 2 with 24.4 °C and the same wet bulb, and 3000 m³/h.
  2. The table gives «Relative humidity φ» 20.79 and 74.1 %, «Humidity ratio ω» 8.581 and 14.23 g/kg and «Enthalpy h» 60.22 and 60.72 kJ/kg. In «Process from 1 to 2»: «Sensible heat» −13.88, «Latent heat» 14.38, «Total heat Δh» 0.4976 kJ/kg, «Sensible heat ratio» −27.9 and «Water to humidify» 18.96 kg/h.
  3. On the chart, line 1 → 2 runs on the dashed 21 °C wet-bulb line. With effectiveness 0.9 the air would leave at 38 − 0.9 · 17 = 22.7 °C: type it in state 2 and φ = 86.12 %.

Example 7Mixing outdoor and return air

A unit mixes 1200 m³/h of outdoor air at 32 °C and 55 % with 3600 m³/h of return air at 24 °C and 50 %, at sea level. Find the humidity ratio, the enthalpy, the temperature and the relative humidity of the mixture.

Solution

  1. Outdoor (1): g/kg, kJ/kg and m³/kg, so kg/h. Return (2): , , and kg/h.
  2. With the dry-air flows (not the volume flows), the outdoor fraction is ; g/kg and kJ/kg.
  3. The temperature comes from : by trial, °C. Averaging the temperatures with the dry-air flows gives 25.94 °C: almost the same.
  4. kPa, with kPa at 25.96 °C: = 52.69 %.
  5. Energy balance: the outdoor air loses kW and the return air gains kW. The mixture carries 5566 kg/h of dry air, in 4800 m³/h: the volume flows almost add up.
= 11.05 g/kg, = 54.23 kJ/kg, = 25.96 °C and = 52.69 %.

Solve it in Simuveliq

  1. The button opens state 1 = outdoor air (32 °C, 55 %) and 2 = return air (24 °C, 50 %), with 1200 m³/h: «Dry air» 1352 kg/h is the outdoor dry air. The table has ω, h and v of both; the process cards are not used here.
  2. Line 1 → 2 on the chart is the mixing line: the mixture lies on it, 24.3 % of the way from 2 to 1.
  3. Check the mixture: in state 2 change the «Second property» to «Humidity ratio ω» and type 25.96 °C and 11.05 g/kg: «Enthalpy h» 54.23 kJ/kg, «Relative humidity φ» 52.71 % (from the rounding of ω) and «Total power» −7.559 kW, what the outdoor air gives to the mixture. Point 2 stays on the previous line: the «Sensible heat ratio» is still 0.311.

Example 8Flow and state of the supply air

A room is kept at 24 °C and 50 % with a 12 kW sensible load and 3 kW latent, at sea level. The air is supplied at 14 °C. Find the sensible heat ratio, the humidity ratio and relative humidity of the supply air, the dry-air flow and the supply volume flow.

Solution

  1. SHR = 12/(12 + 3) = 0.8. The supply air enters at 14 °C and leaves at the room state: ω = 9.301 g/kg and h = 47.77 kJ/kg.
  2. Sensible heat per kg: . With g/kg (checked afterwards) that is 10.195 kJ/kg, and kg/s.
  3. Latent heat per kg: kJ/kg , so g/kg and g/kg.
  4. At 14 °C, kPa and = 83.44 %; m³/kg and m³/h.
  5. The room line has a slope of (9.301 − 8.299)/10 = 0.1002 g/kg per degree; the tool's protractor, at 24 °C, gives 0.1028 for SHR = 0.8: almost parallel (the protractor uses and instead of the exact split). With colder air less flow would be needed, and drier; the line meets saturation at 10.62 °C, the limit.
SHR = 0.8; at 14 °C, ω = 8.299 g/kg and φ = 83.44 %; 1.177 kg/s of dry air and 3493 m³/h of supply.

Solve it in Simuveliq

  1. The button opens state 1 = supply (14 °C with «Humidity ratio ω» 8.299) and 2 = room (24 °C, 50 %), with 3493 m³/h at state 1.
  2. «Process from 1 to 2»: «Sensible heat» 10.2 kJ/kg, «Latent heat» 2.549, «Sensible heat ratio» 0.8; «Dry air» 4237 kg/h (1.177 kg/s), «Sensible power» 12 kW, «Latent power» 3.001 kW and «Total power» 15 kW. «Water to humidify» 4.245 kg/h is here the vapor from the people that the air takes away.
  3. In the table, state 1 has «Relative humidity φ» 83.44 % and «Dew point» 11.24 °C. On the chart, compare line 1 → 2 with the 0.8 radius of the protractor.

Related topics