Simuveliq

Moist-air psychrometric calculator

Type the dry-bulb temperature and one more property (relative humidity, wet bulb, dew point, humidity ratio or enthalpy) and get every moist-air property at sea level, at the altitude of your city or at the pressure you measure. With a second state, compute the sensible, latent and total heat of a process and, with the flow, the power in kW.

Theory and worked examples: Psychrometrics and the psychrometric chart.

What you can do

Frequently asked questions

What is the difference between wet bulb and dew point?

The dew point is the temperature at which air starts to condense when cooled at constant humidity; the wet bulb, that of a wet thermometer in an air stream. The wet bulb is always greater than or equal to the dew point.

Why does the psychrometric chart change with altitude?

At lower pressure, the same relative humidity means more vapor per kg of dry air: at 2600 m, 18 °C and 60 % give 10.6 g/kg against 7.7 g/kg at sea level.

How is the humidity ratio computed?

ω = 0.622 · p_v/(P − p_v), with p_v the vapor pressure (relative humidity times the saturation pressure) and P the air pressure.

Guide: psychrometrics, moist air step by step

The air we breathe is a mixture of dry air and water vapor. Psychrometrics studies that mixture and is the basis of air conditioning, drying, cooling towers and thermal comfort. This guide explains the properties of moist air, how they are computed and works three examples with the same numbers the calculator gives.

The properties

Two independent properties and the pressure fix the state. The calculator always asks for the dry-bulb temperature and one more.

Example 1: an office at 24 °C and 50 % at sea level

  1. Saturation pressure at 24 °C: psat = 2.986 kPa (water tables).
  2. Vapor pressure: pv = 0.50 · 2.986 = 1.493 kPa.
  3. Humidity ratio: ω = 0.622 · 1.493/(101.325 − 1.493) = 0.00930 kg/kg = 9.30 g/kg.
  4. Enthalpy: h = 1.006·24 + 0.00930·(2501 + 1.86·24) ≈ 47.8 kJ/kg of dry air.
  5. Volume: v = 0.287·297.15·(1 + 1.608·0.00930)/101.325 ≈ 0.854 m³/kg.
  6. Dew point: the temperature with psat = 1.493 kPa, 12.9 °C. A window colder than that fogs up.

The calculator gives ω = 9.30 g/kg, h = 47.8 kJ/kg, v = 0.854 m³/kg, dew point 12.95 °C and wet bulb 17.06 °C.

Example 2: a cooling coil

2000 m³/h of air enter at 30 °C and 60 % and leave at 14 °C and 95 %. With the calculator (Second state ticked):

Example 3: altitude changes the result

At 18 °C and 60 %, at sea level ω = 7.70 g/kg; at 2600 m (73.75 kPa in the standard atmosphere), the same relative humidity gives ω = 10.63 g/kg, 38 % more, and the volume goes from 0.835 to 1.153 m³/kg. The vapor pressure and the dew point are the same (10.1 °C), but everything measured per kg of dry air changes. That is why a high city needs its own pressure or a chart for its altitude.

How to use the calculator

  1. Choose the pressure: the altitude (standard atmosphere) or the measured barometric pressure.
  2. Type the dry-bulb temperature and choose the other property: relative humidity, wet bulb, dew point, ω or enthalpy.
  3. For a process, tick Second state, type the final state and, if you want the powers, the air flow at state 1.
  4. The point (or the process line) appears on the complete psychrometric chart at that pressure.

Common mistakes

Further reading

The chapters on gas–vapor mixtures and air conditioning of any engineering thermodynamics textbook, and the psychrometrics chapter of the ASHRAE fundamentals handbook.

More tools

Versión en español

© 2026 Simuveliq. All rights reserved.