T (°C)Vapor P sat (kPa)Humidity ratio W_s (g/kg dry air)Enthalpy h_s (kJ/kg dry air)Volume v_s (m³/kg dry air)Density (kg/m³)
0.010.61173.7779.4570.77851.289
50.87265.40318.580.79481.265
101.2287.63129.260.8121.241
151.70610.6541.990.83031.217
202.33914.757.380.85011.194
253.1720.0976.250.87191.17
304.24727.2199.660.89641.146
355.62936.581290.92431.121
407.38548.891660.95691.096
459.59565.06213.20.99561.07
5012.3586.342741.0431.042
6019.95152.44581.1750.9807

Saturated air (100 % relative humidity). W = 0.621957·p_s/(P − p_s), with 0.621957 = M_water/M_air. For another relative humidity φ: p_v = φ·p_s and W = 0.621957·p_v/(P − p_v). Enthalpy referred to dry air at 0 °C and liquid water at 0 °C (as ASHRAE). Computed by Simuveliq.

Source: CoolProp (MIT license): reference equation of state of water (IAPWS-95) and ideal-gas cₚ of air, the same as the «Thermodynamic tables» tab. ↗

More tables

Liquid water at 1 atm · Dry air at 1 atm · Standard atmosphere · Engineering materials (typical values) · Physical constants and standard values · SI prefixes · Common elements · Molar masses of common compounds · Weak acids and bases (25 °C) · Acid–base indicators · Heating values of fuels (25 °C) · Steel pipe (ASME B36.10M) · ASME B16.5 flanges: outer dimensions · Butt-weld elbows (ASME B16.9): center to end · Threads: tap drill and clearance hole · Rolling bearings: standard dimensions of 9 types (ISO 15, ISO 355, ISO 104) · AWG wire · Twist drills (ASME B94.11M) · O-rings (SAE AS568) · Sheet-metal gauges · Steel I and H sections (IPE, HEA, HEB, HEM, W) · Steel hollow sections (CHS and RHS)

More tools

Versión en español

© 2026 Simuveliq. Todos los derechos reservados.